TECHNICAL SPEC SHEET:
    Specifications:
    • Gnerator power
      TRI-PHASE, 50 Hz, PHI 0,8
      Standby Power (LTP)Prime Power (PRP)
      Power kVA4440
      Power kW3532
      Rotations per minute RPM1500
      Voltage V400
      DimensionsCanopyOpen
      L x l X H (cm)L x W X H (cm)220 x 100 x 110
      Weight (kg)840570
      Fuel tank (L)90
      General specifications

      Power explanations according to ISO 8528 standard:

      Ambient conditions according to standard ISO 8528-1: 2005: 1000 mbar, 25ºC, 30% relative humidity

      Prime Power (PRP)

      Maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours per year according to ISO 8528. 10% overload capability is available for a period.

      Emergency Standby Power (ESP)

      Maximum power at variable load under the operating conditions for which a generator set is capable of delivering, up to 200 operating hours per year, according to ISO 8528. Overload is not allowed.

      • Mitsubishi
      • S4S DT 61SD
      • Diesel
      • 39
      • 4 - in line
      • 3.33
      • 94 X 120
      • 17:01
      • Natural
      • Mechanic
      • Water cooling
      • 12 V
      • 1500 / 50
      • 9.5
      • 9.5
      • 5.3
      • 7.4
      • 9.6
      • Leroy Somer
      • 50
      • 230 / 400
      • 3
      • 0,8
      • H
      • 1
      • Electronic (AVR)
      • ± %0,5
      • 23
      • brush-less and self-excited
    • Energen standby generator sets comply with European standards:

      -2006/42/EC Machinery Directive;
      -2014/35/EU Low voltage Directive;
      -2014/30/EU Electromagnetic Compatibility;
      -2000/14/EC Noise level for outdoor equipment (completed by Directive 2005/88/EC);
      -EN ISO 12100:2010, EN ISO 13857:2008, EN 60204-1:2006/AC:2010;

      Production facilities: Romania

       

      STANDARD for ENERGEN generator sets:

      ▪ Industrial diesel engine & alternator

      ▪ High quality mechanical components, with protections

      ▪ Control panel with digital control mode

      ▪ Chassis, canopy and alternator painted in electrostatic field

      ▪ Emergency stop button

      ▪ Industrial exhaust muffler with noise attenuator

      ▪ Anti-corrosion treated steel chassis

      ▪ Alternator class H insulation, self-excited, brush-less

      ▪ Anti-vibration systems

      ▪ Automatic voltage adjustment (electronic AVR)

      ▪ Steel chassis with integrated fuel tank

      ▪ Mechanical or electronic speed regulator

      ▪ Fuel level indicator (analogic)

      ▪ Cooling system with radiator mounted on engine